The examples below are extracted from DIALux lighting models. They all show realistic contemporary lighting scenarios that could be considered typical for each environment.

The models show that the E4.8 requirement for 100 lux on the face of the signs can be met by normal electrical lighting.

The models should not be taken as evidence that any particular situation will comply with E4.8; light-meter measurements or a specific lighting model should be used for each situation.

Note that all these scenarios are for spaces where daylight would significantly increase the lux figures during the daytime, but the models have deliberately looked at the night-time situation because this is the worst-case scenario.

Factory / Workshop

Lights: Thorn 96218712+96218749+96218754+96218756 CONCAVIA L 1x250W HIE IP23 LI + CONCAVIA L RAL WD + CONCAVIA L KIT COVER GL IP65 + CONCAVIA L KIT WG
Maintained minimum illuminance on work plane: 450
Maintained minimum illuminance on Ecoglo Exit signs: 130
Specific connected load: 11.6 W/m2| 2.6 W/m2/100lux

Small Retail / Cafe

Lights: Thorn 96 202 807 GARBO C 26W TC-TEL HF [STD] Maintained minimum illuminance on work plane: 120
Maintained minimum illuminance on Ecoglo Exit signs: 160
Specific connected load: 7.7 W/m2 | 6.3 W/m2/100lux

Warehouse

Lights: High Five 6x54W
Maintained minimum illuminance on work plane: 170
Maintained minimum illuminance on Ecoglo Exit signs: 120
Specific connected load: 5.5 W/m2| 2.7 W/m2/100lux

Typical Classroom with Recessed Ceiling Lighting

Lights: Thorn FQC2236+FQCP312FR Quattroc Body 2x36WT26HF E3TX WL4/3 L0+Quatttroc diffuser EFL 300s1200mm
Maintained minimum illuminance on work plane: 270
Maintained minimum illuminance on Ecoglo Exit signs: 120
Specific connected load: 9.3 W/m2 | 2.5 W/m2/100lux

Classroom with Surface Mounted Ceiling Lighting

Lights: Thorn 96205778 College 2x28W HF PC CL [STD] Maintained minimum illuminance on work plane: 250
Maintained minimum illuminance on Ecoglo Exit signs: 230
Specific connected load: 8.2 W/m2 | 2.3 W/m2/100lux

Office

Lights: Thorn FQCZ236+FQCP312FR QUATTROC BODY 2X36WT16HF E3TX WL4/3 L0 + QUATTROC DIFFUSER EFL 300x1200mm
Maintained minimum illuminance on work plane: 360
Maintained minimum illuminance on Ecoglo Exit signs: 120
Specific connected load: 10.5 W/m2| 2.9 W/m2/100lux